5. You have a PLC program that reads a sensor value as a 16-bit integer but needs to display it as a floating-point number with two decimal places. Which sequence of data conversion instructions is best to achieve this?
hard
A. INT_TO_REAL(sensor_value) then multiply by 0.01
B. REAL_TO_INT(sensor_value) then divide by 100
C. INT_TO_BOOL(sensor_value) then convert to REAL
D. BOOL_TO_INT(sensor_value) then multiply by 100
Solution
Step 1: Convert integer sensor value to real
Use INT_TO_REAL to convert the 16-bit integer to a floating-point number.
Step 2: Adjust scale for decimal places
Multiply the real number by 0.01 to shift decimal two places for display.
Final Answer:
INT_TO_REAL(sensor_value) then multiply by 0.01 -> Option A
Quick Check:
Convert int to real, then scale for decimals [OK]
Hint: Convert int to real first, then scale for decimals [OK]
Common Mistakes:
Trying to convert real to int first
Using boolean conversions incorrectly
Multiplying before converting data type